TE Connectivity / KISSLING 300A Series 31 Industrial Power Relays

TE Connectivity's (TE) / KISSLING 300A Series 31 Industrial Power Relays are bistable relays designed to operate in harsh environments. The series features electronic functions for pulse-coil protection, a low-energy switching input for direct connection to an electronic control unit (ECU), and an optional "energy" function for fail-safe shutoff when power is lost. TE KISSLING Series 31 power relays are offered in 300A variants and in three control types: ENERGY, INIT, and SAFETY. These robust relays are designed for battery management and power distribution applications.

Features

  • Industrial bistable relays
  • IP67/IP6K9K (steam cleaning) sealing
  • Contact voltages up to 250VDC with magnetic blowout, magnetic blowout required over 40VDC
  • Integrated electronics for coil protection and controls
  • Direct connection to ECU
  • Fail-safe shutoff for critical situations  
  • Wide variety of configuration options

Applications

  • Power distribution
  • Remote battery disconnect
  • Battery management
  • HVAC control
  • Auxiliary power systems
  • Battery charge/discharge monitoring

Specifications

  • 100ΜΩ minimum insulation resistance
  • 50ΜΩ insulation resistance after live or environment
  • 1050VAC/1min dielectric withstanding voltage at 50Hz
  • 150mV maximum contact drop, initial
  • 175mV contact drop after life test
  • 300A continuous current
  • 2400A - 1s/600A - 20s overload
  • Approximately 2mA quiescent current
  • 100% duty cycle main contact current rating and continuous current
  • 100,000 switching cycles under full load minimum 
  • 2M mechanical life cycles
  • 6G shock and 4G vibration resistant
  • -40°C to +85°C operating temperature range

Circuits

Application Circuit Diagram - TE Connectivity / KISSLING 300A Series 31 Industrial Power Relays

Ordering Information

Chart - TE Connectivity / KISSLING 300A Series 31 Industrial Power Relays
Published: 2020-04-02 | Updated: 2026-09-14